Bearing Capacity Adjustment Coefficient of Tension Angle Members Connected with One Bolt in Single Shear
-
摘要: 螺栓孔的端距Ld、边距Lz会影响输电铁塔中单颗螺栓连接单角钢构件承载力和其两端节点板尺寸,缩小Ld可降低连接区几何尺寸、减小或取消节点板,增加Ld可提高构件抗拉承载力。目前国内DL/T 5442—2020《输电线路杆塔制图和构造规定》中螺栓Ld、Lz均为固定值。为研究此类构件受拉承载力,进行∟56、∟80、∟90、∟110四种规格角钢单螺栓连接的材性试验和受拉试验,角钢材质为Q235B,高强螺栓直径16,24 mm,设置位移计测量试件变形和孔伸长量。试件加载后螺栓孔发生塑性变形而纵向伸长,达极限拉力时受压孔壁两侧及对应的角钢端面中部撕裂。依据试件参数建立连接板、角钢、螺栓的有限元模型,各部件接触面附近网格尺寸小于2 mm。
计算结果表明:有限元模型的高应力区与试件破坏区域相同,二者极限拉力平均相差5.8%,荷载-孔伸长量曲线与位移计测量结果相符。采用屈服强度fy=235 MPa、弹性模量E=2.06×105 MPa的钢材计算四组单螺栓(Ld=(0.8~3.7)d0)连接角钢模型:∟40×3、1M12,∟×3、1M16,∟50×4、1M16,∟63×5、1M20。
结果表明:螺孔直径大于螺杆的造成单剪连接时受压孔壁应力集中,在试件总伸长量较小时部分区域已产生塑性变形,随后试件失去初始刚度,螺栓孔不断伸长。模型采用基准端距时构件承载力Nrt约为DL/T 5486—2020《架空输电线路杆塔结构设计技术规定》中承载力Ncode的95%,四组试件的受拉承载力Nt约为极限拉力Nu的75%,国内DL/T 5486—2020有一定裕度。试件荷载-孔伸长量曲线的线性段长度、刚度变化位置、承载力受Ld和Lz共同影响,以Ld/Lz=1.5为分界主要发生两种破坏模式:小于临界值时试件发生端部剪切、撕裂破坏;超过临界值后逐渐转变成角钢净截面破坏,继续提高Ld对承载力影响不大。国内∟40角钢目前使用M16螺栓,采用M12螺栓后降低Lz/d0,可获得更高的承载力上限。EC 3、ASCE等标准中考虑了Ld、Lz对受拉承载力的影响,其材料强度等参数取值主要针对当地钢材,公式形式复杂。结合我国钢材的实际情况、输电铁塔计算框架,根据试验和模型结果给出包含承载力调整系数的计算方法,考虑了Ld与Lz的不同影响,对不同螺杆直径、角钢肢宽的构件用同一算式计算,适用于Ld=(1.0~3.0)d0范围内单螺栓单剪连接的热轧角钢构件受拉承载力计算。Abstract: The end distance Ld and edge distance Lz of bolt holes affect the bearing capacity of single angle steel members connected by a single bolt and the size of gusset plates at both ends in the transmission tower. Reducing Ld can reduce the geometric size of the connection area, reduce or cancel the gusset plate, and increasing Ld can improve the tensile bearing capacity of members. At present, the bolt Ld and Lz in DL/T 5442-2020 are fixed values. In order to study the tensile bearing capacity of such members, the material property test and tensile test of single bolt connection of angle steel of ∟56, ∟80, ∟90 and ∟110 specifications were carried out. The angle steel is made of Q235 B, and the diameters of high-strength bolt are 16 mm and 24 mm. Displacement meters were set to measure the member deformation and hole elongation. After the specimen was loaded, the bolt hole had plastic deformation and longitudinal elongation. When the ultimate tension was reached, both sides of the pressure hole wall and the middle of the end surface of the corresponding angle steel were torn. The finite element model of connecting plate, angle steel and bolt was established according to the test piece parameters, and the grid size near the contact surface of each component was less than 2 mm.
The calculation resuls show that the distribution of high stress areas are identical for specimens and FEA models, and the average error of ultimate tension foce between the two is 5.8%, and the load-hole elongation curves are consistent with the test results. Four groups of one bolt connected angle models(Ld=(0.8~3.7)d0) are built for further study with yield strength fy=235 MPa and elastic modulus E=2.06×105 MPa:∟40×3, 1 M12, ∟40×3, 1 M16, ∟50×4, 1 M16, ∟63×5, 1 M20.
The results show that the diameter of the bolt hole is larger than that of the bolt, resulting in the stress concentration on the compression hole wall during the single shear connection. When the total elongation of the specimen is small, plastic deformation has occurred in some areas, and then the specimen loses its initial stiffness, and the bolt hole continues to elongate. When the reference end distance is adopted, the bearing capacity Nrt of the specimen is about 95% of the DL/T 5486-2020 bearing capacity Ncode, and the tensile bearing capacity Nt of the four groups of specimens is about 75% of the ultimate tensile force Nu. There is a certain margin in DL/T 5486-2020. The length of the linear section of the load-hole elongation curve, the position of stiffness change and the bearing capacity of the specimen are jointly affected by Ld and Lz. Taking Ld/Lz=1.5 as the boundary, there are mainly two failure modes:when it is less than the critical value, the specimen has end shear and tear failure; after exceeding the critical value, it gradually turns into the net section failure of steel angle, and the continuous increase of Ld has little effect on the bearing capacity. At present, M16 bolts are used for ∟40 angle steel in China. When M12 bolts are used, Ld/d0 can be reduced to obtain a higher upper limit of bearing capacity. EC 3, ASCE and other specifications consider the influence of Ld and Lz on tensile bearing capacity. The values of material strength and other parameters are mainly for local steel, and the formula form is complex. Combined with the actual situation of steel in China and the calculation framework of transmission tower, the calculation method including bearing capacity adjustment coefficient is given according to the test and model results. Considering the different effects of Ld and Lz, the same calculation formula is used for members with different bolt diameters and steel angle leg widths, which is suitable for the calculation of tensile bearing capacity of hot-rolled steel angle members connected by single bolt and single shear within the range of Ld=(1.0~3.0)d0. -
[1] 杨隆宇.Q420高强度厚板焊接大规格角钢轴压稳定承载力研究[J].钢结构(中英文),2019,34(10):43-47. [2] 杨隆宇.Q420厚板焊接大规格角钢残余应力峰值及分布[J].电力勘测设计,2019(8):25-29. [3] 国家能源局.输电线路杆塔制图和构造规定:DL/T 5442-2020[S].北京:中国计划出版社,2020. [4] 中国铁塔股份有限公司.低成本铁塔标准图集:Q/ZTT 1029-2020[S].北京:中国铁塔股份有限公司,2020. [5] 潘斌,石永久,王元清.Q460等级高强度钢材螺栓抗剪连接孔壁承压性能有限元分析[J].建筑科学与工程学报,2012,29(2):48-54,95. [6] 石永久,潘斌,施刚,等.高强度钢材螺栓连接抗剪性能试验研究[J].工业建筑,2012,42(1):56-61. [7] Kim T S,Hong S K,Hwang B K,et al.Block shear capacity in cold-formed lean duplex stainless steel double-shear bolted connections[J].Thin-Walled Structures,2021,161(6).DOI: 10.1016/j.tws.2021.107520. [8] Mai B V,Cao H P,Hancock G J,et al.Block shear strength and behaviour of cold-reduced G450 steel bolted connections using DIC[J].Journal of Constructional Steel Research,2019,157(1):151-160. [9] Hwang B K,Kim T S.An Investigation on ultimate strength of high strength aluminum alloys four-bolted connections with out-of-plane deformation[J].International Journal of Steel Structures,2018,19(4):1158-1170. [10] Li C,Jiang Y,Qiao R,et al.Modeling and parameters identification of the connection interface of bolted joints based on an improved micro-slip model[J].Mechanical Systems and Signal Processing,2021:153.DOI: 10.1016/j.ymssp.2020.107514. [11] 杨隆宇,施菁华,李妍.螺栓单面连接不等边角钢轴压承载力试验研究[J].钢结构,2018,33(4):1-6. [12] Snijder H H,Ungermann D,Stark J,et al.Evaluation of test results on welded connections in order to obtain strength functions and suitable model factors.part A:results.part B:evaluations.Eurocode 3[S].Brussels:Commission of the European Communities,1988. [13] CEN.Eurocode 3:Design of steel structures-Part 1-8:BS EN 1993-1-8[S].Brussels:European Committee for Standardisation,2005. [14] ASCE.Design of latticed steel transmission structures:ASCE 10-15[S].New York:American Society of Civil Engineers,2015. [15] 中华人民共和国国家质量监督检验检疫总局.金属材料拉伸试验第1部分:室温试验方法:GB/T 228.1-2010[S].北京:中国标准出版社,2011. [16] 国家能源局.架空输电线路杆塔结构设计技术规定:DL/T 5486-2020[S].北京:中国计划出版社,2020. [17] 中华人民共和国住房和城乡建设部.钢结构设计标准:GB 50017-2017[S].北京:中国建筑工业出版社,2018.
点击查看大图
计量
- 文章访问数: 214
- HTML全文浏览量: 56
- PDF下载量: 27
- 被引次数: 0